The framework: ITC AEM 1 "Ascensores"
Royal Decree 355/2024 of 2 April approved the complementary technical instruction ITC AEM 1 "Ascensores", in force since 1 July 2024. It governs the commissioning, modification, maintenance and inspection of lifts, as well as improving the safety of existing lifts. It replaces the instruction approved by Royal Decree 88/2013.
Maintenance frequency
Maintenance is carried out by an authorised maintenance company (empresa conservadora), with which the owner must have a contract:
- Every four months: lifts in single-family homes and certain lifts in residential buildings with up to three stops serving no more than 20 dwellings.
- Every month: all other lifts, with between 20 and 45 days between one visit and the next.
Periodic inspections
In addition to maintenance, an inspection body checks the lift periodically:
- Every 2 years: industrial buildings and buildings open to the public.
- Every 4 years: buildings with more than 20 dwellings or more than four floors.
- Every 6 years: all other lifts.
Each autonomous community sets out the procedure for reporting these inspections: check the one for your region.
The owner's obligations
- Keep the lift in good working order for as long as it is used.
- Have a maintenance contract with a maintenance company.
- Commission the periodic inspection, which the maintenance company itself cannot carry out.
- Prevent the lift from operating if it is known not to offer safety guarantees.
- Bear, according to the statutes and decisions of the owners' association, the mandatory safety upgrades.
Preventive and corrective maintenance
Preventive maintenance is the periodic visits: testing the safety chain, brakes and door protection, lubrication, adjustments and wear checks. Corrective maintenance restores the lift to working order after a fault, with small or large repairs.
Good preventive maintenance reduces corrective work. The parts that deteriorate most without maintenance are well known: traction ropes or belts, brakes, sheave bearings and shafts, oxidised electronic components, valves on hydraulic lifts and safety devices that trip for no reason.
Existing lifts
The ITC AEM 1 provides for measures to improve the safety of existing lifts, which are checked during inspections. A modernisation (controller, drive, doors, operating panels) is often the best opportunity to carry them out. We supply the equipment, and your installation or maintenance company fits it.